Supply
|
| Voltage |
12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
| Current Consumption |
60 mA with 20 mA output and transistors energized. |
| Power Dissipation |
1.3 W with 24 V supply, 20 mA output and transistors energized. |
| Max. power consumption |
at 30 V supply voltage, overload condition, transistors output energized and PPC1090 connected, 1.9 W. |
Input
|
| Type |
magnetic pick-up, contact, proximity to EN60947-5-6, open-collector transistor for frequency signal up to 50 KHz, TTL CMOS. |
| Magnetic pick-up sensitivity |
≥ 20 mVpp up to 100 Hz input, ≥ 50 mVpp up to 1 KHz, ≥ 100 mVpp up to 5 KHz, ≥ 500 mVpp up to 20 KHz, ≥ 1 Vpp up to 50 KHz. |
| Switching current levels |
ON ≥ 2.1 mA, OFF ≤ 1.2 mA, switch current ≈ 1.65 mA ± 0.2 mA hysteresis (for proximity or transistor input). |
| Equivalent source |
8 V 1 KΩ typical (8 V no load, 8 mA short circuit). |
| Integration time |
100 ms |
| Resolution/Visualization |
1 mHz for 50 Hz range, 10 mHz for 500 Hz range, 100 mHz for 5 KHz range, 1 Hz for 50 KHz range. |
| Input range |
0 to 50.5 KHz maximum. |
Burnout
|
| Type |
downscale analog output signal for loss of input signal. |
Output
|
| Type |
0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V. |
| Resolution |
1 µA current output or 1 mV voltage output. |
| Transfer characteristic |
linear direct or reverse. |
| Response time |
≤ 50 ms (10 to 90 % step change). |
| Output ripple |
≤ 20 mVrms on 250 Ω load. |
Repeater Output
|
| Type |
voltage free SPST optocoupled open-collector transistor. |
| Output factor |
direct 1:1 or divided by 10, 100, 1000, 10000, 100000 or 1000000. |
| Open-collector rating |
100 mA at 35 Vdc (≤ 1.5 V voltage drop). |
| Leakage current |
≤ 50 µA at 35 Vdc |
| Frequency response |
50 KHz maximum |
Alarm
|
| Trip point range |
within rated limits of input range (see input for step resolution). |
| Delay time |
0 to 1000 s, 100 ms step. |
| Hysteresis |
0 to 5 Hz for 50 Hz range, 0 to 50 Hz for 500 Hz range, 0 to 500 Hz for 5 KHz range, 0 to 5 KHz for 50 KHz range (see input visualization parameters for step resolution). |
| Output |
voltage free SPST optocoupled open-collector transistor. |
| Open-collector rating |
100 mA at 35 Vdc (≤ 1.5 V voltage drop). |
| Leakage current |
≤ 50 µA at 35 Vdc. |
Input performance
|
| Type |
Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. |
| Calibration and linearity accuracy |
≤ ± 0.05 % of full scale of selected input range. |
| Temperature influence |
≤ ± 0.005 % of full scale input range for a 1 °C change. |
Output performance
|
| Type |
Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. |
| Calibration accuracy |
≤ ± 0.1 % of full scale |
| Linearity error |
≤ ± 0.05 % of full scale. |
| Supply voltage influence |
≤ ± 0.05 % of full scale for a min to max supply change. |
| Load influence |
≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change. |
| Temperature influence |
≤ ± 0.01 % on zero and span for a 1 °C change. |
Isolation
|
| Test Voltage |
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Digitals Out 500 V; Digital Outs/Supply 500 V; Digital Out/Digitals Out 500 V; |
Environmental conditions
|
| Operating |
temperature limits –20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. |
| Storage |
temperature limits – 45 to + 80 °C. |
Safety description
|
| Safety parameters |
Uo/Voc = 10.9 V, Io/Isc = 1.1 mA, Po/Po = 3 mW at terminals 13-16. Uo/Voc = 15.5 V, Io/Isc = 13 mA, Po/Po = 48 mW at terminals 14-15. Uo/Voc = 10.9 V, Io/Isc = 23 mA, Po/Po = 60 mW at terminals 15-16. Ui/Vmax = 30 V, Ci = 0 nF, Li = 0 nH at terminals 13-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C. |
Mounting
|
| Type |
EN/IEC60715 TH 35 DIN-Rail. |
| Weight |
about 155 g. |
| Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
| Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
| Protection class |
IP 20. |
| Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |