Supply
|
| Voltage |
12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
| Current Consumption |
70 mA @ 24 V for 2 channels D1052D, 45 mA for 1 channel D1052S with 20 mA output typical. |
| Power Dissipation |
1.5 W for 2 channels D1052D, 1.0 W for 1 channel D1052S with 24 V supply voltage and 20 mA output typical. |
| Max. power consumption |
at 30 V supply voltage, overload condition and PPC1090 connected, 2.1 W for 2 channels D1052D, 1.4 W for 1 channel D1052S. |
Input
|
| Type |
0/4 to 20 mA (-4 to +24 mA reading) separately powered input, voltage drop ≤ 0.5 V or 0/1 to 5 V or 0/2 to 10 V (-2 to +12 V reading) 1 MΩ impedance. |
| Integration time |
100 ms. |
| Resolution |
1 µA on current input, 1 mV on voltage input. |
| Visualization |
1 µA on current input, 1 mV on voltage inpu |
| Input range |
-4 to +24 mA on current input, -2 to +12 V on voltage input. |
Burnout
|
| Type |
enabled or disabled. Analog output can be programmed to detect burnout condition with downscale or highscale forcing. |
| Range |
low and high separated trip point value programmable between -5 to +25 mA on current input and -3 to +13 V on voltage input. |
Output
|
| Type |
0/4 to 20 mA, on max. 600 Ω load source mode, current limited at 22 mA or 0/1 to 5 V or 0/2 to 10 V signal, limited at 11 V. |
| Resolution |
2 µA current output or 1 mV voltage output. |
| Transfer characteristic |
linear or reverse. |
| Response time |
≤ 50 ms (10 to 90 % step change). |
| Output ripple |
≤ 20 mVrms on 250 Ω load |
Alarm
|
| Trip point range |
within rated limits of input sensor (see input for step resolution) |
| Delay time |
0 to 1000 s, 100 ms step. |
| Hysteresis |
0 to 5 mA on current or 0 to 5 V on voltage (see input for step resolution). |
| Output |
voltage free SPST relay contact. |
| Contact rating |
2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). |
Input performance
|
| Calibration accuracy |
≤ ± 20 µA on current input or ≤ ± 10 mV on voltage input. |
| Temperature influence |
≤ ± 2 µA, 1 mV of input for a 1 °C change. |
Output performance
|
| Calibration accuracy |
≤ ± 20 µA on current input or ≤ ± 10 mV on voltage input. |
| Linearity error |
≤ ± 0.05 % of full scale |
| Supply voltage influence |
≤ ± 0.05 % of full scale for a min to max supply change |
| Load influence |
≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change. |
| Temperature influence |
≤ ± 0.01 % on zero and span for a 1 °C change. |
Isolation
|
| Test Voltage |
I.S. In/Outs 1.5 KV; I.S. In/Supply 1.5 KV; Analog Out/Supply 500 V; Analog Out/Alarm Outs 1.5 KV; Alarm Outs/Supply 1.5 KV; Alarm Out/Alarm Out 1.5 KV. |
Environmental conditions
|
| Operating |
temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. |
| Storage |
temperature limits – 45 to + 80 °C. |
Safety description
|
| Safety parameters |
Uo/Voc = 10.8 V, Io/Isc = 4 mA, Po/Po = 11 mW at terminals 14-15-16. Ui/Vmax = 30 V, Ci = 4.5 nF, Li = 0 nH at terminals 14-15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60°C. |
Mounting
|
| Type |
EN/IEC60715 TH 35 DIN-Rail. |
| Weight |
about 160 g. |
| Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
| Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
| Protection class |
IP 20. |
| Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |