Supply
|
| Voltage |
24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
| Current Consumption |
25 mA typical. |
| Power Dissipation |
0.6 W with 24 V supply voltage and fault relay energized, typical. |
| Max. power consumption |
at 30 V supply voltage and fault relay energized, 0.9 W. |
Input
|
| Type |
24 Vdc nom (20.4 to 27.6 Vdc) reverse polarity protected. |
| Current Consumption |
50 mA with relay energized, typical. |
| Power Dissipation |
1.2 W with 24 V input voltage and relay energized, typical. |
| Max. power consumption |
at 27.6 V input voltage and relay energized, 1.5 W. |
Output
|
| Type |
voltage free relay contact, normally open. |
| Contact material |
Ag Alloy (Cd free). |
| Contact rating |
3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load). |
| Contact inrush current |
5 A at 30 Vdc, 250 Vac. |
| Contact min. switching current |
10 mA. |
| DC Load breaking capacity |
See Instruction Manual |
| Mechanical / electrical life |
50 * 106 / 1 * 105 operation, typical. |
| Operate / release time |
5 / 3 ms typical. |
| Bounce time NO / NC contact |
3 ms. |
| Frequency response |
10 Hz maximum. |
Fault detection
|
| De-energized fault signal |
≤ 100 μA continuous (typical 65 μA). |
| De-energized open output detection |
load resistance ≥ 350 KΩ (current ≤ 30 μA). |
| De-energized no fault detection |
load resistance ≤ 250 KΩ |
| Energized open output detection |
load current ≤ 10 mA (no fault detection ≥ 25 mA). |
| Fault signalling |
voltage free NE SPST relay contact (output de-energized in fault condition). |
| Contact rating |
3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load). |
| Response time |
200 ms typical. |
Isolation
|
| Test Voltage |
Output/Input 2.5 KV; Output/Supply 2.5 KV; Output/Fault Output 2.5 KV; Input/Supply 500 V; Input/Fault Output 500 V; Fault Output/Supply 500 V. |
| Storage |
temperature limits –20 to + 60 °C, relative humidity max 95 %. |
Environmental conditions
|
| Operating |
temperature limits –20 to + 60 °C, relative humidity max 95 %. |
| Storage |
temperature limits - 45 to + 80 °C. |
| Connection |
about 155 g. |
| Location |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
| Protection class |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
| Dimensions |
IP 20. |
Mounting
|
| Type |
EN/IEC60715 TH 35 DIN-Rail. |
| Weight |
about 155 g. |
| Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
| Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
| Protection class |
IP 20. |
| Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |