FEATURES
- SIL 2 / SC 3
- Output to Zone 0/Div. 1
- Installation in Zone 2/Div. 2
- 4-20 mA Input, Output Signal
- HART® compatible
- Line & Load short/open circuit detection
- Field fault mirroring to the PLC AO
- In-field programmability by DIP Switch
- High Accuracy
- Three port isolation, Input/Output/Supply
Technical Data
Supply
|
| Voltage |
24 Vdc nom (18 to 30 Vdc), reverse polarity protected |
| Current Consumption |
35 mA @ 24 Vdc with 20 mA output on 500 Ω load, typical. |
| Power Dissipation |
0.65 W @ 24 Vdc with 20 mA output on 500 Ω load, typical. |
Input
|
| Type |
4 to 20 mA with ≤ 2.5 V voltage drop, reverse polarity protected in normal operation, ≥ 5 kΩ impedance (≈ 2 mA sinking from 10 to 30 Vdc) when fault condition detected. |
Output
|
| Type |
4 to 20 mA, on max. 700 Ω load. |
| Response time |
25 ms (0 to 100 % step change). |
Fault
|
| Type |
Field device and wiring open circuit or short circuit detection; short circuit detection can be disabled via dip-switch. |
| Short output |
load resistance < 50 Ω or < 100 Ω dip-switch selectable (≈ 2 mA forcing to detect fault). |
| Open output |
load resistance > (21 V / Loop current) -300 Ω (for example, if Loop current = 20 mA: load resistance > (21 V / 20 mA) -300 Ω = 750 Ω). |
| Fault signaling |
voltage free NE SPST optocoupled open-collector transistor (output de-energized in fault condition). |
| Open-collector/drain rating |
100 mA @ 35 Vdc (≤ 1.5 V voltage drop). |
| Leakage current |
≤ 50 μA @ 35 Vdc. |
| Response time |
≤ 30 ms. |
Performance
|
| Ref. Conditions |
24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. |
| Calibration accuracy |
≤ ± 0.1 % FSR. |
| Linearity accuracy |
≤ ± 0.1 % FSR. |
| Temp. influence |
≤ ± 0.01 % FSR on zero/span for a 1 °C change. |
Isolation
|
| Test Voltage |
I.S. Out/In 2.5 kV; I.S. Out/Supply 2.5 kV; I.S. Out/Fault 2.5 kV; I.S. Out/I.S. Out 500 V; In/Supply 500 V; In/In 500 V; Fault/In 500 V; Fault/Supply 500 V; Fault/Fault 500 V. |
Environmental conditions
|
| Operating temperature |
temperature limits –40 to +70 °C. |
| Storage temperature |
temperature limits –45 to +80 °C. |
Safety description
|
| Equipment |
Associated apparatus and non-sparking electrical equipment. |
| Safety parameters |
Uo = 25.9 V, Io = 93 mA, Po = 595 mW at terminals 7-8, 9-10. Um = 250 Vrms or Vdc, -40 °C ≤ Ta ≤ 70 °C. |
Mounting
|
| Type |
DIN-Rail 35 mm, with or without Power Bus or on custom Term. Board. |
| Weight |
about 130 g |
| Connection |
by polarized plug-in disconnect screw terminal blocks to accommodate terminations up to 2.5 mm² (13 AWG). |
| Dimensions |
Width 12.5 mm, Depth 123 mm, Height 120 mm. |
| Shipping weight: |
0,50 kg
|
| Item weight: |
0,30 kg
|
| Dimensions
( Length × Width × Height ):
|
16,00 × 14,00 × 14,00 cm |
| Zustand / Condition: |
Neu / New |
Product safety information
Manufacturer information:
G.M. International srl
Via G. Mameli 53-55
Monza e Brianza
Villasanta, Italien, 20852
info@gminternational.com
https://gminternational.com/