FEATURES
- SIL2 /SC3
- Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
- High Density, two channels per unit.
- NO/NC contact/proximity Detector Input.
- Two SPDT Relay Output Signals.
- SPDT Relay Output for fault detection on single chammel version.
- Three port isolation, Input/Output/Supply.
- EMC Compatibility to EN61000-6-2, EN61000-6-4, EN1326-1
- In-field programmability by DIP Switch.
- 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
Technical Data
Supply
|
Voltage |
24 Vdc nom (20 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp |
Current Consumption |
60 mA with input closed and relays energized |
Power Dissipation |
1.4 W with 24 V supply voltage, input closed and relays energized. |
Max. power consumption |
at 30 V supply voltage, short circuit input and relays energized, 1.8 W |
Input
|
Type |
ON ≥ 2.1 mA, OFF ≤ 1.2 mA, switch current ≈ 1.65 mA ± 0.2 mA hysteresis. |
Fault current levels |
open fault ≤ 0.2 mA, short fault ≥ 6.8 mA (when enabled both faults de-energize channel relay with dual channel unit D1030D or actuate fault relay with single channel unit D1030S). |
Input equivalent source |
8 V 1 KΩ typical (8 V no load, 8 mA short circuit). |
Output
|
Type |
voltage free SPDT relay contact. |
Contact material |
AgCdO. |
Contact rating |
2 A 250 Vac 500 VA, 2 A 250 Vdc 80 W (resistive load). |
DC Load breaking capacity |
see instruction manual. |
Mechanical / electrical life |
30 * 106 / 1 * 105 operation, typical |
Operate / release time |
7 / 3 ms typical. |
Bounce time NO / NC contact |
3 / 5 ms. |
Response time |
20 ms. |
Frequency response |
10 Hz maximum. |
Isolation
|
Test Voltage |
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; Out/Supply 1.5 KV; Out/Out 1.5 KV. |
Environmental conditions
|
Operating |
temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C |
Storage |
temperature limits -45 to + 80 °C. |
Safety description
|
Safety parameters |
UKR TR n. 898: 2ExnAnCiaIICT4 X, ExiaI X Uo/Voc = 10.7 V, Io/Isc = 15 mA, Po/Po = 39 mW at terminals 13-14, 15-16. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
Mounting
|
Type |
EN/IEC60715 TH 35 DIN-Rail |
Weight |
about 135 g |
Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
Protection class |
IP 20 |
Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |
Shipping weight: |
0,50 kg
|
Item weight: |
0,30 kg
|
Dimensions
( Length × Width × Height ):
|
16,00 × 14,00 × 14,00 cm |
Zustand / Condition: |
Neu / New |
Product safety information
Manufacturer information:
G.M. International srl
Via G. Mameli 53-55
Monza e Brianza
Villasanta, Italien, 20852
info@gminternational.com
https://gminternational.com/