FEATURES
- SIL2 /SC3
- Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
- High Density, two channels per unit.
- 4-20 mA Input, Output Signal.
- HART® compatible.
- Input and Output short circuit proof.
- High Accuracy.
- Three port isolation, Input/Output/Supply.
- EMC Compatibility to EN61000-6-2, EN61000-6-4, EN61326-1
- In-field programmability by DIP Switch.
- 250 Vrms (Um) max. voltage allowed to the instruments associated with the barrier.
STATUS
PHASE-OUT
Next: SPARE-ONLY (2027-01-01)
ALTERNATIVE PRODUCT
Technical Data
Supply
|
| Voltage |
12-24 Vdc nom (10 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
| Current Consumption |
110 mA with 20 mA output typical |
| Power Dissipation |
1.8 W with 24 V supply voltage and 20 mA output typical |
| Max. power consumption |
at 30 V supply voltage and short circuit condition, 3.4 W |
Input
|
| Type |
4 to 20 mA (2 wire Tx current limited at ≈ 25 mA). |
| Transmitter line voltage |
≥ 15.0 V at 20 mA with max. 20 mVrms ripple on 0.5 to 2.5 KHz frequency band. |
Output
|
| Type |
4 to 20 mA, on max. 600 Ω load in source mode; V min. 5 V at 0 Ω load V max. 30 V in sink mode, current limited at ≈ 25 mA or 1 to 5 V on internal 250 Ω shunt (or 2 to 10 V on internal 500 Ω shunt on request). |
| Response time |
20 ms (10 to 90 % step change). |
| Output ripple |
≤ 20 mVrms on 250 Ω communication load on 0.5 to 2.5 KHz band. |
| Frequency response |
0.5 to 2.5 KHz bidirectional within 3 dB (HART® protocol). |
Performance
|
| Type |
Ref. Conditions 24 V supply, 250 Ω load, 23 ± 1 °C ambient temperature. |
| Calibration accuracy |
≤ ± 0.1 % of full scale. |
| Linearity error |
≤ ± 0.1 % of full scale. |
| Supply voltage influence |
≤ ± 0.05 % of full scale for a min to max supply change. |
| Load influence |
≤ ± 0.05 % of full scale for a 0 to 100 % load resistance change. |
| Temperature influence |
≤ ± 0.01 % on zero and span for a 1 °C change. |
Isolation
|
| Test Voltage |
I.S. In/Out 1.5 KV; I.S. In/Supply 1.5 KV; I.S. In/I.S. In 500 V; Out/Supply 500 V; Out/Out 500 V. |
Environmental conditions
|
| Operating |
temperature limits -20 to + 60 °C, relative humidity max 95 %. |
| Storage |
temperature limits - 45 to + 80 °C. |
Safety description
|
| Safety parameters |
Uo/Voc = 25.2 V, Io/Isc = 93 mA, Po/Po = 585 mW at terminals 14-15, 10-11. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
Mounting
|
| Type |
EN/IEC60715 TH 35 DIN-Rail. |
| Weight |
about 170 g |
| Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
| Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
| Protection class |
IP 20. |
| Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |
| Shipping weight: |
0,50 kg
|
| Item weight: |
0,30 kg
|
| Dimensions
( Length × Width × Height ):
|
16,00 × 14,00 × 14,00 cm |
| Zustand / Condition: |
Neu / New |
Product safety information
Manufacturer information:
G.M. International S.p.A
Via G. Mameli 53-55
Monza e Brianza
Villasanta, Italien, 20852
info@gminternational.com
https://gminternational.com/
Important Notice!
Our items are generally not new. They come from inventory liquidations and dismantlings.
Please note that for items where no age information is provided in the description, it should be assumed that they have been stored for a very long time, possibly several years. This can affect the quality and durability of technical items. Please consider this before making a purchase.