FEATURES
- Input from Zone 0 (Zone 20), Division 1, installation in Zone 2, Division 2.
- Voltage input with isolated commands, loop powered or bus powered.
- Suitable for driving 1 or 2 positions directional solenoid valves.
- Output short circuit proof and current limited.
- Three port isolation, Input/Output/Supply.
- EMC Compatibility to EN61000-6-2, EN61000-6-4.
- 250 Vrms (Um) max. voltage allowed to the Instruments associated with the barrier.
Technical Data
Supply
|
| Voltage |
24 Vdc nom (21.5 to 30 Vdc) reverse polarity protected, ripple within voltage limits ≤ 5 Vpp. |
| Current Consumption |
140 mA @ 24 V with output energized at nominal load, 160 mA @ 24 V with short circuit output. |
| Power Dissipation |
2.0 W with 24 V supply voltage, output energized at nominal load. |
| Max. power consumption |
at 30 V supply voltage and short circuit output, 4.2 W. |
Input
|
| Type |
switch contact, logic level or loop powered. |
| Trip voltage levels |
OFF status ≤ 1.0 V, ON status ≥ 6.0 V (maximum 30 V) |
| Current Consumption |
3 mA @ 24 V(≈ 10 KΩ input impedance). |
Output
|
| Type |
100 mA at 13.7 V (20.5 V no load, 68.1 Ω series resistance) at terminals 13-14, 9-10. (For more details see the Instruction manual) |
| Short circuit current |
≥ 110 mA (115 mA typical) |
| Response time |
20 ms (power up in 600 ms typical in loop powered mode). |
Isolation
|
| Test Voltage |
I.S. Out/In 1.5 KV; I.S. Out/Supply 1.5 KV; In/Supply 500 V; In/In 500 V. |
Environmental conditions
|
| Operating |
temperature limits -20 to + 60 °C, relative humidity max 90 % non condensing, up to 35 °C. |
| Storage |
temperature limits – 45 to + 80 °C |
Safety description
|
| Safety parameters |
Uo/Voc = 23.6 V, Io/Isc = 366 mA, Po/Po = 1600 mW at terminals 13-14, 9-10. Um = 250 Vrms, -20 °C ≤ Ta ≤ 60 °C. |
Mounting
|
| Type |
EN/IEC60715 TH 35 DIN-Rail. |
| Weight |
about 130 g. |
| Connection |
by polarized plug-in disconnect screw terminal blocks to accomodate terminations up to 2.5 mm2. |
| Location |
Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4, Class I, Division 2, Groups A, B, C, D Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA T4 installation. |
| Protection class |
IP 20. |
| Dimensions |
Width 22.5 mm, Depth 99 mm, Height 114.5 mm. |
| Versandgewicht: |
0,50 kg
|
| Artikelgewicht: |
0,20 kg
|
| Abmessungen
( Länge × Breite × Höhe ):
|
16,00 × 14,00 × 14,00 cm |
| Zustand / Condition: |
Neu / New |
Angaben zur Produktsicherheit
Herstellerinformationen:
G.M. International srl
Via G. Mameli 53-55
Monza e Brianza
Villasanta, Italien, 20852
info@gminternational.com
https://gminternational.com/